WHT-08交聯(lian)電(dian)纜(lan)外(wai)護(hu)套故障測試(shi)儀可以(yi)進行(xing)下(xia)列測(ce)試:中(zhong)高壓屏蔽(bi)電(dian)纜(lan)上(shang)的護(hu)套故障預(yu)定(ding)位(wei)、塑(su)料(liao)絕(jue)緣(yuan)層(ceng)低壓電(dian)纜(lan)上(shang)線(xian)路接(jie)地(di)故障預(yu)定(ding)位(wei)、采用測(ce)量(liang)跨(kua)步電(dian)壓(ya)法(fa)可(ke)以(yi)對(dui)電(dian)纜(lan)故障進行(xing)定(ding)點。
由於全波整(zheng)流實現了優(you)良(liang)的轉換(huan)效(xiao)應(ying),此(ci)設備(bei)非(fei)常(chang)適(shi)合(he)於(yu)將(jiang)低壓電(dian)力(li)電(dian)纜(lan)中(zhong)的高阻(zu)電(dian)纜(lan)故障轉換(huan)為(wei)低阻故障。
新型護(hu)套探測(ce)器(qi)具(ju)有(you)的特(te)性:
連(lian)續(xu)可(ke)調(tiao)的輸出(chu)電(dian)壓(ya),電(dian)壓(ya)範(fan)圍(wei):2000V、4000V、6000V 和10000 V;
通(tong)過(guo)電(dian)壓(ya)和電(dian)流控(kong)制(zhi)實(shi)現(xian)過(guo)載保護(hu);
低功(gong)率(lv)故障定(ding)位(wei),以(yi)避(bi)免(mian)損(sun)壞(huai)相(xiang)鄰線(xian)路或(huo)電(dian)纜(lan);
通(tong)過(guo)來模擬(ni)表(biao)頭來顯示(shi)電(dian)壓(ya)和電(dian)流;
自動(dong)放(fang)電(dian)裝(zhuang)置提供(gong)了清除(chu)殘(can)余電(dian)荷(he)和將測(ce)試物體(ti)接地(di)的功(gong)能(neng);
通(tong)過(guo)全波整(zheng)流得(de)到了良(liang)好的高阻(zu)故障轉換(huan)效(xiao)果(guo);
二(er)、外(wai)護(hu)套測試(shi)儀的主(zhu)要(yao)功(gong)能(neng):
(1)反(fan)射法(fa)的有(you)力補(bu)充,粗測結(jie)果(guo)更(geng)準確(que),可(ke)靠(kao)性高(gao)。
(2)有(you)效(xiao)解(jie)決波傳(chuan)播(bo)特(te)性不(bu)好的PVC聚氯乙烯電(dian)纜(lan)、無(wu)銅(tong)屏蔽(bi)低壓電(dian)纜(lan)故障的主(zhu)要(yao)手段(duan)。
(3)測(ce)試電(dian)壓(ya)細分(fen)為(wei)2000V,4000V,10000V三(san)檔,適用於(yu)不同(tong)電(dian)壓(ya)等(deng)級(ji)的電(dian)纜(lan)。
(4)測(ce)量(liang)範圍(wei)無(wu)盲(mang)區。
(5)降(jiang)壓到零後的儀器(qi)自動(dong)放(fang)電(dian)功(gong)能(neng)。
(6)適用於(yu)380V-220kV高、中(zhong)、低壓電(dian)力(li)電(dian)纜(lan)的故障預(yu)定(ding)位(wei)。
(7)適用於(yu)380-1000V電(dian)纜(lan)跨(kua)步電(dian)壓(ya)法(fa)時(shi)的定(ding)點。
(8)適用於(yu)66kV-220kV電(dian)纜(lan)外(wai)護(hu)套故障的預(yu)定(ding)位(wei)和定(ding)點。
(9)WHT-08高壓(ya)發(fa)生(sheng)器(qi)同(tong)時(shi)是(shi)電(dian)纜(lan)故障轉換(huan)儀,可講高(gao)達500兆(zhao)歐(ou)姆的疑(yi)難(nan)高阻故障轉換(huan)為(wei)低阻故障。
交聯(lian)電(dian)纜(lan)外(wai)護(hu)套故障測試(shi)儀圖片
三(san)、測(ce)試(shi)原理:
地(di)埋(mai)電(dian)纜(lan)外(wai)護(hu)套故障的測尋(xun),同電(dian)力(li)電(dian)纜(lan)故障探測(ce)壹樣,壹般要經(jing)過(guo)“初測(ce)”和“定(ding)點”二(er)個(ge)步驟。外(wai)護(hu)套接地(di)故障的初測(ce)(測(ce)距)壹般采用壓(ya)降法(fa)和電(dian)橋法(fa)測(ce)試(shi)。由於電(dian)橋法(fa)測(ce)試(shi)有(you)局限(xian)性,不(bu)能(neng)測試(shi)多(duo)點接地(di)故障,也不能(neng)測試(shi)三(san)相(xiang)電(dian)纜(lan)鏈式接(jie)地(di)連(lian)線(xian)的故障。本儀器(qi)是(shi)針對(dui)外(wai)護(hu)套故障的特(te)點,采用壓(ya)降法(fa)初測(ce)電(dian)纜(lan)外(wai)護(hu)套的接地(di)故障,再用跨(kua)步電(dian)壓(ya)法(fa)查找(zhao)故障點,通(tong)過(guo)兩(liang)根(gen)接(jie)地(di)鐵釬,尋(xun)找土壤(rang)中(zhong)電(dian)勢(shi)zui低點而定(ding)點。在(zai)故障點處(chu)流入(ru)大地(di)的測試(shi)電(dian)流導(dao)致故障點處(chu)為(wei)正負(fu)電(dian)壓(ya)峰(feng)值(zhi)轉換(huan)點,在(zai)故障點前接(jie)近故障時(shi),跨(kua)步電(dian)壓(ya)增(zeng)加(jia),越(yue)過(guo)故障後跨(kua)步電(dian)壓(ya)減小,並且極(ji)性改(gai)變(bian)。在(zai)接地(di)故障點正上(shang)方時(shi),指(zhi)針停(ting)在(zai)零位(wei),此(ci)處(chu)既為(wei)電(dian)纜(lan)故障點的準確(que)位(wei)置。儀器(qi)用於(yu)交聯(lian)電(dian)纜(lan)的外(wai)護(hu)套故障探測(ce);也可用於(yu)地(di)埋(mai)線(xian)和全塑(su)線(xian)(無金屬(shu)護(hu)層(ceng)電(dian)纜(lan))故障的探測(ce);還(hai)可用作(zuo)電(dian)纜(lan)或(huo)其(qi)它(ta)電(dian)器(qi)的10KV直流耐壓試驗(yan)。
交聯(lian)電(dian)纜(lan)外(wai)護(hu)套故障測試(shi)儀接收機(ji)圖片
四、技(ji)術性能(neng):
電(dian)源(yuan)輸出(chu)方式 :直(zhi)流、脈(mai)動(dong)2種方式可(ke)選(xuan)
直(zhi)流電(dian)壓(ya)輸出(chu) :電(dian)壓(ya)0至10kV可調(tiao) 短(duan)路電(dian)流50-500mA
直流電(dian)流輸出(chu):50mA-500mA
電(dian)壓(ya)比(bi)較法(fa)為(wei) :±2% L
定(ding)點精度(du):跨(kua)步電(dian)壓(ya)法(fa)定(ding)點 ±30cm
電(dian)話
微信(xin)掃壹掃